Edge AI aims to continuously optimize the supply temperature by using
the building’s thermal inertia, outdoor climate, weather forecasts, and indoor
climate data in order to achieve a more stable average indoor temperature.
Active mode is indicated by a green-colored cloud. When activated, the heating circuit’s heating curve factor is replaced by a new one from Edge AI and is then updated every 10 minutes.
The optimized curve factor is calculated based on the base curve factor defined further down in this menu
Inactive mode is indicated by a gray-colored cloud. When Edge AI is inactive, the base curve from this menu is copied to the heating circuit.
- Inactivate Edge AI and wait until the cloud turns gray
- Adjust the base curve factor further down in this menu and click save
- Activate Edge AI again; the new base curve factor will now be used for the next
optimization, and the cloud should turn green shortly
If indoor sensors are included in the optimization in Edge, a manual adjustment
of the heating curve factor may counteract Edge AI’s optimization.